The C-TEC XFP 2 Loop 32 Zone Addressable Fire Alarm Panel is a high-performance device offered at a competitive price. Certified by LPCB to EN54 parts 2 and 4, this panel comes in a robust metal enclosure with keypad or keyswitch entry for Access Levels 2 and 3, and supports Apollo's XP95/Discovery protocol. It's perfect for both small and large applications, with the capability to network up to 8 XFP master panels, making it a popular choice in Europe.
Key Features:
- EN54-2/4 certification by LPCB.
- Compatible with Apollo XP95/Discovery protocol.
- Two programmable conventional sounder circuits.
- One fault output relay and three programmable relays with changeover contacts.
- Various zone dependency/coincidence functions.
- Day/night function for occupied/unoccupied buildings.
- Alarm counter for tracking alarm occurrences.
- Robust loop drivers supporting up to 40 loop powered 10mA sounders per loop.
- Built-in EN54-4/A2 switch mode power supply.
- Delay function for investigation periods.
- Easy access to Access Levels 2 and 3 via keypad/keyswitch.
- User-friendly Windows-based PC program for upload-download.
- Optional accessories include a flush-mounting bezel and a glazed stainless steel enclosure.
- Networking capability for up to eight XFP main panels on a RS485 network, or connection of up to eight XFP repeaters to a single main panel.
Technical Specification:
Approvals/Certifications:
- Certified to EN54-2 and EN54-4 by the Loss Prevention Certification Board (LPCB).
Protocol/Compatibility:
- Compatible with Apollo XP95/Discovery systems.
Mains Supply:
- 230V AC, 50/60Hz.
Mains Rated Current:
- Maximum 680mA.
Internal Power Supply:
- Nominal 27V DC.
Total Output Current:
- Limited to 3A at 230V AC (Imax.A 270mA; Imin. 70mA).
Quiescent Current:
- 100mA with 2 loops unloaded.
Battery Specifications:
- Maximum size: 2 x 12V, 7Ah VRLA, connected in series.
Loop Drivers:
- Number: 2.
- Maximum output current: 500mA (25V minimum; 34V maximum).
- Maximum loop length: 1KM.
- Maximum addressable devices per loop: 126.
Sounder Circuits:
- Number of conventional circuits: 2.
- Maximum circuit length: 500m.
- End-of-Line (EOL) resistor value: 6800Ω 5% Tolerance, 0.25W (color code: blue, grey, red, gold).
- Maximum sounder output current: 400mA.
Auxiliary Relays:
- 3 x Programmable Relays (configurable from C&Es).
- 1 x Fault Relay (active when no faults are present), volt-free single pole changeover.
- Maximum switch current: 1A.
- Maximum switch voltage: 30V DC.
Other Outputs:
- 24V Auxiliary Power (19.5V minimum, 28V maximum), protected by a resettable fuse.
- Maximum current: 100mA.
Auxiliary Inputs:
- 2 x Programmable Inputs (configurable from C&Es), trigger by connecting to 0V.
- Maximum input voltage: 27V (non-latching).
PC Connection:
- Via RS232 molex connector (included in XFP507 upload/download software kit); no printer connection.
Indicators:
- 2-line x 40-character backlit display.
- 32 Zonal LEDs.
- Indicators for General Fire, Energized, Pre-Alarm, Remote Output Activated/Disabled, Accessed, Disablement, Test, Silenced, General Fault, System Fault.
Connections:
- Fixed, maximum conductor size 1mm².
Expansion Connections:
- 2-wire RS485 network/repeater connection via optional AFP711 network card.
- Maximum 8 mains per network or 8 repeaters per non-networked main.
- Distance limit: 1KM for main panel network, 500M for repeater network.
Product Dimensions:
- Width: 410mm, Height: 250mm, Depth: 80mm (base dimensions).
Operating conditions for temperature range from -5ºC to +40ºC, with a maximum relative humidity of 95%.
Ryontechs is your trusted partner for life protection systems, including comprehensive fire safety solutions, in East Africa. We are committed to delivering superior quality products at competitive prices, ensuring quick delivery for your convenience. Our professional services extend to expert installation of all our products, ensuring your safety and security. Contact us at 0798888608 to learn more or to place your order.
C-TEC XFP 2 Loop 32 Zone Addressable Fire Alarm Panel
- Brand: C-TEC
- Product Code: Fire System
- Availability: In Stock
-
KES157,000